Sensitron Smart P-2 Fixed Car Park Gas Detector
A fixed car park gas detector which can simultaneously detect CO and NO2 gases or CO and petrol vapours.
Sensitron Smart P-2 Fixed Car Park Gas Detector Overview
The Sensitron Smart P-2 Gas Detection System is used to detect the presence of combustible and toxic gases in non-classified areas.
The Sensitron P-2 uses catalytic sensors to detect petrol vapours and electrochemical cells for the detection of CO and NO2 toxic gases in closed carparks and tunnels.
A combination of high traffic in underground car parks coupled with inadequate ventilation can cause toxic gases such as carbon monoxide (CO), nitrogen dioxide (NO2) and petrol vapours to build up and can be extremely harmful to pedestrians in shared spaces. It is important to continuously monitor the level of toxic gases in these confined spaces by using a fixed car park gas detector to reduce or eliminate health and safety risks to people in closed car parks.
Sensitron SMART P-2 Car Park Multi-Gas Detection System with Extension Kit
Petrol vapours and NO2 are heavier gases than air and they tend to spread downward. For NO2 detection, the gas detector should be placed 30 cm from the floor to maximise the effectiveness of the detection.
Whereas the weight of carbon monoxide (CO) is similar to air. To detect CO in a carpark or tunnel, the gas detector should be placed at breathing level, approximately 1.50 m above the floor. The CO+PETROL VAPOUR detector comes with an extension kit to mount the Petrol Vapour sensor 30 cm off the ground and the CO head at nose level.
Correct detector positioning is essential to ensure prompt and accurate detection. (Figure 1)
Figure 1: Sensitron Smart P-2 Fixed Car Park Gas Detector with Petrol Vapour Extension Kit
The detector works autonomously and automatically. Once adequately connected, no further operations are required.The flashing green LED on the motherboard indicates the detector’s working condition. During normal status, the LED blinks with the frequency 1s ON - 1s OFF.
If you require a reliable fixed car park gas detector that can detect only CO and NO2 check out the Sensitron SMART P-1
For more information on the Sensitron Smart P-2 Gas detector contact your local Air-Met office.
Sensitron Smart P-2 Car Park Gas Detector Features
- Standard RS485 communication
- Ongoing system self-diagnosis
- Easy sensor replacement
- IP rating: IP55
- Can operate in extreme temperatures of -20 °C and up to 50 °C
Sensitron Smart P-2 Fixed Car Park Gas Detector Specifications
Sensor | |||
Application | Car Parks | ||
Sensing element |
Catalytic sensor for petrol vapours |
||
Predicted sensor lifetime |
Catalytic: 4 / 5 years EC: 2 / 3 years |
||
Gas detected | CO, NO2, petrol vapours | ||
Fullscale |
Petrol vapours: 0 - 100% LFL |
Electrical Data | |||
Power supply | 12-24 Vdc | ||
Output |
RS485 serial output |
||
Predicted sensor lifetime | EC: 2 / 3 years | ||
Absorption |
S2400CO-ND: 32 mA at 24 Vdc |
Environmental conditions | |||
Storage temperature | 0 / +20°C up to six months | ||
Operating temperature |
-20 / +50°C |
||
Operating humidity | 15 /90 %RH |
External case | |||
Material |
Enclosure: Polycarbonate |
||
Dimensions |
Box: 100 x 100 x 52 mm |
||
Weight | 250 g | ||
Cable entries |
2 x M20 |
||
IP Grade | IP 55 | ||
Remote head cable length | 1.5 m |
Compliance | |||
EMC EN |
50270:2015 | ||
Car park standard | EN 50545-1:2011 |
Sensitron Smart P-2 Car Park Gas Detector Applications
- To monitor carbon monoxide, nitrogen dioxide and petrol vapours in underground car park.
Sensitron Smart P-2 Fixed Car Park Gas Detector Support Documents
Sensitron Smart P-2 Data Sheet Sensitron Smart P Car Park Gas Detectors User Manual Sensitron Smart P Gas Detectors Instruction Manual