OLCT100 Toxic And Combustible Gas Detector
Designed For The Detection Of Explosive Gases, Toxic Gases Or Oxygen.
SKU
OLCT100
The Oldham OLCT 100 Fixed Gas Detector has been designed for the detection of explosive gases, toxic gases or oxygne with 4-20mA output.
Available in explosion-proof or intrinsically safe versions, the OLC(T) 100 is suitable for detection of all gases in ATEX zones.
Regardless of your application, Air-Met's range of Oldham Fixed Gas Detectors offers a solution: catalytic, electrochemical, semiconductor, or poison control version. ATEX approved, these detectors are available in explosion safe or intrinsically safe versions.
In addition to this range the OLCT 100 offers an infrared sensor, which allows it to be used in more severe environmental conditions, where the presence of poisons could harm the use of a catalytic sensor. With a 3-year warranty on the sensor and electronics, the OLCT 100 XP-IR will provide reliability and extended lifetime.
SIL 2 certified according to EN 50402, the 100 series is very safe. As an example the Probability of Failure on Demand (PFD) of combustible versions is 1 out of 418 for the catalytic version and 1 out of 2857 for the infrared version.
Contact Air-Met Scientific today for more information.
Features of the OLCT 100 Fixed Gas Detector Includes:
-
4-20 mA analogue transmitter without display
-
SIL2 capability for LEL, O2, CO, H2S, NH3, CO2
-
Detects combustible, toxic or refrigerant gases and O2
-
Available with electrochemical, infrared or semi-conductor sensors
-
Designed for industrial applications
-
Available in explosion-proof or intrinsically safe versions, and stainless steel
-
A high-temperature version allows operation up to 200°C
OLCT 100 Specifications | ||||||
---|---|---|---|---|---|---|
Model | OLCT 100 XP | OLCT 100 XP IR | OLCT 100 XP | OLCT 100 XP HT | OLCT 100 XP | OLCT 100 IS |
Sensor | Catalytic Bead | Infrared | Electrochemical | Catalytic Bead | Semi-Conductor | Electrochemical |
Material |
Epoxy-coated aluminium housing (Inox 316L optional). 316 stainless steel sensors
|
|||||
Dimensions (mm) | 135 x 133 x 84 | 179 x 138 x 84 | 179 x 138 x 84 | 150 x 138 x 84 | 179 x 138 x 84 | 179 x 138 x 84 |
Weight (kg) | 1 | 1.1 | 1.1 | 1.8 | 1.1 | 1.1 |
Ingress Protection | IP66 | |||||
Cable Entry | M20 or 3/4 NPT | |||||
Supply Voltage | 15.5 to 32 VDC | 13.5 to 32 VDC | 10 to 32 VDC | 15.5 to 32 VDC | 15.5 to 32 VDC | 15.5 to 32 VDC |
Average Consumption | 110 mA | 60 mA | 23.5 mA | 100 mA | 100 mA | 23.5 mA |
Pressure | atmostpheric +/- 10% | |||||
Output Signal |
Usual source encoded from 0 to 23 mA (not isolated)
- linear 4 to 20 mA output, reserved for measurement
- 0 mA : electronic fault or no power supply
- < 1 mA: fault
- 2 mA: initialisation mode
- > 23 mA: out of range
|
|||||
Approvals |
Compliant with European directive ATEX 94/9/CE and with IECEx schedule for explosion-proof detectors.
OLC 100, OLCT 100 XP, OLCT 100 XP IR : ATEX II 2 GD / Ex d IIC T6 Gb / Ex t IIIC T85°C Db IP66
OLCT 100 IS Aluminium : ATEX II 2 GD / Ex ia IIC T4 / Ex iaD 21 T135°C IP66
OLCT 100 IS Stainless Steel : ATEX II 1 GD / Ex ia IIC T4 / Ex iaD 20 T135°C IP66
SIL 2 according to EN 50402 / EN 61508 for catalytic and infrared versions, O2, CO, NH3 and H2S
SIL 2 according to EN 50402 / EN 61508
Metrological performances according to EN/IEC 60079-29-1
Electromagnetic compatibility according to EN 50270
|
|||||
Cable |
3 active wires,
shielded cable
|
3 active wires,
shielded cable
|
2 active wires,
shielded cable
|
3 active wires,
shielded cable
|
3 active wires,
shielded cable
|
2 active wires,
shielded cable
|
- Steel mills
- Petrochemical facilities
- Chemical industry
- Pharmaceutical industry
- Food industry
- Refrigeration industry
- Water treatment