OLCT 20 Fixed Gas Detector

Indoor and Outdoor Gas Detection for Flammable, Toxic Gases and Oxygen Measurements.

SKU
OLCT20
Only 0 left
The OLC(T) 20 Series of gas detectors are designed for indoor or outdoor facility monitoring and other applications to accommodate your gas detection requirements at a reasonable price.
 
OLC(T) 20 Detector
The new generation of OLC 20 combustible sensors are unaffected by poisons. The units provide extremely quick response times and complete reliability. They can be fitted on a housing with a M25 or 3/4" NPT thread.
 
The stainless steel detector provides protection and resistance to corrosive agents. Classified IP 66, they are resistant to dust and water ingress. The pre-calibrated sensors of the OLCT 20 can be disconnected by turning the head of the unit. These “smart” sensors can be calibrated on a work bench, outside hazardous areas.
For more information on the OLCT 20 Fixed Gas Detector, contact your local Air-Met office. 
 
  • Designed for indoor or outdoor monitoring
  • Complete reliability
  • SIL2 suitable for combustible gases and O2
  • Can be fitted on a housing with a M25 or 3/4” NPT thread
  • Stainless steel detector provides protection and resistance to corrosive agents
  • The pre-calibrated sensors can be disconnected by turning the head of the unit
DetectorOLCT20
Type XP Transmitter IS Transmitter
Gas Detection Principle
Catalytic/ Electrochemical  
Detected Gases Flammable, toxics and oxygen  
Sensor Housing Stainless steel type 316 L Stainless steel type 316 L Stainless steel type 316 L
Pre-Calibrated Sensor yes yes
Power Supply at the Detector 15 to 30 VDC (catalytic) 15 to 30 VDC (chemical) 10 to 26 VDC
Maximum Power Consumption
100 mA (catalytic) 25 mA (chemical)
25 mA
Output Signal 4-20 mA 4-20 mA
Load Impedance 250 Ω (catalytic) Depending on power supply (chemical) 47 Ω max
Wiring 3 reinforced wires (catalytic) 2 reinforced wires (chemical) 2 reinforced wires
Loop Impedance with ISC Monitor
32 Ω (catalytic) (1 km with 1,5 mm) 128 Ω (chemical) (4 km with 1,5 mm)
32 Ω (1 km with 1,5 mm)
Wiring Connection Delivered with a 6mm-diameter cable
Fastening
M25 thread to screw or 3/4’’ NPT
M25 thread to screw or 3/4’’ NPT
 
 
 
 
Ingress Protection IP 66 IP 66
Certification EEx d IIC T6 II 2 GD INERIS 01 ATEX 0004X EEx ia IIC T4 II 1 GD INERIS 01 ATEX 0004X
CEM Mark EN 50270 EN 50270
Weight 800 g
Dimensions L 130 x D 60
L 130 x D 60
Operating Temperature (for electronic) -25°C to +60°C -25°C to +60°C
  • Offshore E&P
  • Power Stations
  • Steel Production
  • Food & Beverages